Description
General Features
• Cummins engine 6BTAA5.9-G12
• Close coupled to Leroy Somer alternator LSA44.3L10
• Microprocessor control module PLC-7420
• Main circuit breaker: 250A
• Rotate speed governor: ECU
• Excitation system: Self excited,SHUNT
• A.V.R model: R250
• Key switch
• Emergency stop switch
• ATS (automatic transfer switch) receptacle
• 2x12V/120AH Sealed for life maintenance free battery
• Lockable battery isolator switch
• 50℃ radiator
• Oil pump on the engine
• Steel base frame with lifting lugs
• Vibration isolators between the engine/alternator andbase frame
• Dry type air filter
• Base fuel tank for 8 hours running
• Drain points for fuel tank
• Operation Manual / Specifications
Standards & Conditions
Design Standards
The designs and the productions are in conformity with:
• Conformite Europeenne (CE)
• ISO8528-5:2005
• GB/T2820.5-2009
Environmental Operating Conditions
• Installation place: Outdoors or indoors (well ventilated).
• Ambient temperature:-25℃ to 50℃.The coolant heater
is needed when the temperature is below 5℃
• Humidity: Less than 80%.
• Altitude: Below one thousand (1000) meters.
Factory Inspection
• Inspection items.
• Protection devices working test.
• Starting ability in normal temperature.
• 50%rated power load moment capability.
• Voltage deviation and speed variation: 0%, 25%, 50%,
75%, 100%, 110% Load.
Painting Process
• Painting process andcolorsarebasedon
the manufacturer’s standard.
• The customer could also choose the color which the
manufacturer offers.
(Data Sheet) 150Kva Generator Cummins Engine Stamford alternator